Chapter 4 Parameter Settings|DD Series


4-73

0001B:

1st

accel/decel.

0010B: 2nd accel/decel

0011B: 3rd accel/decel

0100B: 4th accel/decel

0101B: 5th accel/decel

0110B: 6th accel/decel

0111B: 7th accel/decel

1000B: 8th accel/decel

1001B: 9th accel/decel

1010B:

10th

accel/decel

1011B:

11th

accel/decel

1100B:

12th

accel/decel

1101B:

13th

accel/decel

1110B:

14th

accel/decel

1111B: 15th accel/decel

Bit12

1: enable bit06-11 function

Bit13~14

00B: No function

01B: operated by digital keypad

10B: operated by Pr.00-21 setting

11B: change operation source

Bit15

Reserved

2001H

Frequency

command

2002H Bit0

1: EF (external fault) on

Bit1

1:

Reset

Bit2

1: B.B. ON

Bit3~5

Reserved

Status monitor
Read only

2100H Error code: refer to Pr.06-16 to Pr.06-21

2119H

Bit0

Bit1

00: Stop
01: deceleration

Bit2

opening door is prohited,

Bit3

Bit4

00: CD command, OD output
01: CD command, OD output
10: OD command, CD output
11: Reserved

Bit5~7

Reserved

Bit8

1: Master frequency Controlled by communication

interface

Bit9

1: Master frequency controlled by analog/external

terminals signal

Bit10

1: Operation command controlled by communication

interface

Bit11

1: Parameters have been locked

Bit12

1: enable to copy parameter from keypad

Bit13~15

Reserved

2102H Frequency command (F)

2103H Output frequency (H)

2104H

Output

current (AXXX.X)

2105H

DC-BUS

Voltage (UXXX.X)

2106H

Output

voltage (EXXX.X)

2107H Current step number of Multi-Step Speed Operation

2116H Multi-function display (Pr.00-04)

2120H Frequency command when malfunction

2121H Output frequency when malfunction

2122H Output current when malfunction

2123H Motor frequency when malfunction

2124H Output voltage when malfunction

2125H DC-bus voltage when malfunction

2126H Output power when malfunction

2127H Output torque when malfunction

2128H

IGBT

Temperature of Power Module at Present Fault

Advertising