73696050 DH-SMT/SI

VI.AC.K2.3E

© Danfoss 08/2009

5

ENGLISH

Safety Notes

Prior to assembly and commissioning
to avoid injury of persons and damages
of the devices, it is absolutely necessary
to carefully read and observe these
instructions.

Necessary assembly, start-up, and
maintenance work must be performed
only by qualified, trained and authorized
personnel.

Prior to assembly and maintenance work
on the controller, the system must be:
- depressurized,
- cooled down,
- emptied and
- cleaned.

Please comply with the instructions of the

system manufacturer or system operator.

Definition of Application

The electrical actuator is used in
connection with the following valves:
VFG 2(21), VFG 25, VFU 2, VFGS 2, AFQM 6.

Fields of application are the temperature
control of water, water-glycol mixtures
and steam for heating, district heating and
cooling systems.

Wiring

1

End Switch

2

Adjusting the End Switch

3

Only special actuator types are equipped
with end-switch, see rating plate.

Adjusting the End Switch“Stem
extended”
1. Press push-button

until the

valve

is completely closed (VFU 2

completely open) and the direction

indicator

stops.


Observe stroke indicator, it must move

to position

.

2. Connect terminals 14 and 16 to an

ohmmeter

.

3. Turn screw

until the cam

switches

the end-switch

and the ohmmeter

shows 0 Ω.

Potentiometer

4

Potentiometer Settings

5

Only special actuator types are equipped
with potentiometer (as accessories).

After having mounted a valve and an
actuator and after having removed the
mounting screw, carry out the following
steps:

Adjust zero point
1. Press push-button

until the valve

is completely closed (VFU 2

completely open) and the direction
indicator

stops.


Observe stroke indicator, it must move
to position

.

2. Unscrew stroke setting screw

by 2

turns out of the female thread.

3. Press push-button

until the valve

is completely open (VFU 2 completely
closed) and the direction indicator

stops.

4. Press push-button

until the valve

is completely closed (VFU 2 completely
open) and the direction indicator

stops.

The zero point of the potentiometer

is adjusted

5. Then, adjust the stroke.

Note:
The range 0 - 1, 2, 5, 10 kΩ corresponds
to the maximum stroke (20 mm) of the
actuator. After the stroke is adjusted, the
resistance must be measured in accordance
with the valve stroke.