DISPLAYS OF THE INDOOR UNIT,
LED INDICATORS AND CONTROLS

T

: EMERGENCY and RESET button

S

: Receiver of remote control signal

P

: Green LED

R

: Yellow LED

Q

: Red LED

Indoor Unit LEDs

Information about the operating mode of the
indoor unit is given by the 3 LEDs
(light-emitting diodes) on the unit.

THE GREEN LED (P)

indicates the

followings:

Error diagnosis.

During normal operation, the LED is
illuminated.

NOTE

• When the unit is disconnected or in

Standby mode (waiting), the LED
remains switched off. If a breakdown
occurs, the LED flashes at 5-second
intervals. The error code is shown by
the number of times the LED flashes.
A pause of 5 seconds occurs between
the luminous signal cycles.

ERROR CODE

DESCRIPTION

3

Ambient temperature sensor error

4

Indoor unit coil sensor error

7

Outdoor unit error

10

EEPROM malfunction

11

Corrupted serial number

12

Incomplete address/zone information

13

Gas flow distribution error