VMB8IR IR receiver module user manual – version 1

7

CONNECTION


To interconnect the Velbus modules it is recommended to use a twisted-pair cable (EIB 2x2x0.8mm², UTP
4x2x0.51mm² - CAT5 or equivalent).
Make sure to use a heavy-gauge wire (0.5mm

2

or more) in case of a multiple module connection (>10 modules) or

with log connections (>50m).
Connect the bus to the module (mind the polarity).

Termination

Generally, only 2 ‘TERM’ terminators must be used in a complete Velbus

®

installation. Usually, this will be on one

module inside the distribution box and on the module which is physically located furthest from the distribution box.

On all other modules, the terminator must be removed.


Remark:

In case of a wiring with multiple branches, only place a termination into a single module in the distribution box and
in the control panel which is the farthest from the distribution box. When communication problems occur, you can
place an extra termination on another branch. It is highly recommended to limit the number of terminations as too
large a number may overload the bus.