DESCRIPTION

E8950 Modbus-to-BACnet Protocol Converter enables easy integration of a broad
selection of Veris meters with Building Automation Systems via BACnet protocol.
When networked, the E8950 detects supported Modbus meters and gives them
a unique BACnet Device ID and full set of measurement data and configuration
objects. Simply select the desired MS/TP baud rate using DIP switches or configure
the IP interface using the integral web server, and the supported Veris Modbus
meters are available as fully-supported BACnet devices.

APPLICATIONS

Energy Management with Building Automation Systems

Integrated metering of HVAC systems and chillers

Integrate Multiple Modbus

Meters into a BACnet Network

Modbus-to-BACnet

Protocol Converter

E8950

E8950

SPECIFICATIONS

Downstream (Device) Interfaces:

Physical Layer

2-wire RS-485

Line Termination

Internal, 120 Ω

Line Polarization Internal

Protocol

Modbus RTU

Baud Rate

9600 to 38400 (selections vary with Modbus devices used)

Number of Devices Supported

up to 32 devices (not to exceed 1000 total BACnet data objects)

Upstream (Controller) Ethernet Interface:

Physical Layer

10/100 Mb Ethernet

Protocol

BACnet IP

Upstream (Controller) Serial Interface:

Physical Layer

2-wire RS-485

Protocol

BACnet MS/TP

Baud Rate

9600, 19200, 38400, 76800

Input Power Requirements:

Supply Voltage

Class 2 9-30VDC or 12-24VAC

Nominal Current Draw @ 12V 240mA

Environmental:

Operating Temperature Range

-40°C to 122°C (-40°F to 50°F)

Operating Humidity Range

5-90% RH noncondensing

Agency Approvals

CE; TUV approved to UL916

Year

Warranty

2

FEATURES

Enables Veris meter access via BACnet MS/TP and/or BACnet IP...compatible

with standard building protocols

Supports a broad range of Veris meters: H8035, H8036, H8163 with H8163-

CB, H8238, H8436, H8437, E50C2, E51C2, E50C3*, E51C3*, E30Ax42, E30Bxxx,

E30Cxxx, E31Bxxx, E31Cxxx...application flexibility

Each E8950 can support up to 1000 BACnet measurement points (or 32 meters

max., if <1000 total points)...extensive data collection

Simultaneously supports mixed meter types (with common baud rate)...

versatility in the field

Simple to set up...automatically detects supported meters and configures

BACnet objects...no manual mapping of Modbus points required

Presents a separate device object for each meter attached...easy to program

Can be mounted on DIN rail or wall...installation flexibility

* The logging functionality of these meters is not supported.

HQ0001715.D 01131