INSTALLATION GUIDE

H84xx

Power Meters For Use With 1V CTs

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

QUICK INSTALL

1. Mount the device in a fire/electrical enclosure. Use the retaining clips for the

H84xx-V. Use appropriate wall-mounting screws for the H84xx-VB(S).

2. Wire the device. See the Wiring Diagrams section for options.

3. Configure the communications parameters.

Installer’s Specifications

Electrical Characteristics:

Type of measurement

True RMS up to the 15th harmonic. On three-phase AC system

Measurement Accuracy:

Current & Voltage

ANSI C12.16, 0.5%

Power

ANSI C12.16, 1%

Frequency

±-0.01 Hz from 45 to 65 Hz

Data Update Rate

1 sec

Input Voltage Characteristics:

Measured Voltage Max.

UL to 600VAC (L-L); CE to 300VAC (L-N)

Metering Over-Range +20%

Impedance

2 MΩ (L-L)/ 1MΩ (L-N)

Frequency Range

45 to 65 Hz

Input Current Characteristics:

CT Scaling

Primary: Adjustable from 5A to 32,767A

Measurement Input Range

0 to 1.0VAC (+20% over-range)

Impedance

100 kΩ

Control Power*

AC: 100 to 415 ±10%VAC, 5VA; DC: 125 to 250 ±20%VDC, 3W

(see * for 600V option)

Control Power Ride Through Time

100 mS at 120VAC

Output:

Pulse Output #1 H8453V/VB, H8463V/VB

(kWh) N.O., static output

(240VAC or 300VDC, 100mA max. at 25°C,

derate

0.56mA per °C above 25°C) 2.41kV RMS isolation

Pulse Output #2 H8453V/VB

(Phase Detect or kVARh) N.O., static output

(240VAC or 300VDC, 100mA max. at 25°C,

derate

0.56mA per °C above 25°C) 2.41kV RMS isolation

Pulse Output #2 H8463V/VB

(Phase Detect or kVARh) N.C., static output

(240VAC

or 300VDC, 100mA max. at 25°C,

derate

0.56mA per °C above 25°C) 2.41kV RMS isolation

RS485 Port; H8436V/VB; H8437V/VB

2-wire, 2400 to 19200 baud, Modbus RTU

Mechanical Characteristics:

Weight

H8400V=0.81lb; H8400VB=6.35lb; H8400VBS=9.15lb

IP Degree of Protection (IEC 60529)

IP40 front display, meter body IP30 for VB

Display Characteristics

Back-lit green LCD (6 lines total, 4 concurrent values)

Environmental Conditions:

Operating Temperature

Meter: 0° to 60°C; Display: -10° to 50°C

Storage Temperature

Meter and Display: -40° to 85°C

Humidity Range

5 to 95% RH at 50°C (non-condensing)

Metering Category:

North America

CAT III; for distribution systems up to 347V L-N/600VAC L-L

CE

CAT III; for distribution systems up to 300V L-N/480VAC L-L

Dielectric Withstand

Per UL 508, EN61010

Conducted and Radiated Emissions

FCC part 15 Class B, EN55011

Safety:

North America UL508/C22.2

Europe

CE per IEC 61010

*For control voltages >415VAC order H84xxVBS