Installation guide, H84xx default settings, H84xx – Veris Industries H84xx Install User Manual
Page 12

Z204046-0J
PAGE 12
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
12115
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H84xx
INSTALLATION GUIDE
H84XX DEFAULT SETTINGS
Model
H8436X/37x
H8453x
H8463x
CT Primary Ratio
100A
100A
100A
CT Secondary Ratio
1 V
1 V
1 V
PT Ratio
1:1 (none)
1:1 (none)
1:1 (none)
Frequency
60 Hz
60 Hz
60 Hz
Setup Password
00000
00000
00000
Reset Password
00000
00000
00000
Display Mode
IEEE
IEEE
IEEE
System Type
40
40
40
Modbus Address
001
N/A
N/A
Modbus Baud Rate
19200 baud
N/A
N/A
Modbus Parity
None
N/A
N/A
1st Pulse Contact
N/A
N.O.
N.O.
kWh Pulse Width
N/A
100ms
100ms
kWh Pulse Energy Index
N/A
1 kWh/Pulse
1 kWh/Pulse
2nd Pulse Contact
N/A
N.O.
N.C.
2nd Pulse Contact Output
N/A
kVARh
Phase Loss
kVARh Pulse Width
N/A
100ms
100ms
kVARh Pulse Energy Index
N/A
1 kVARh/Pulse
1 kVARh