Veris Industries H931 Datasheet User Manual

Current sensors with relay: 4-20ma analog output, Load trending and control relay in one package, Current monit oring

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

DESCRIPTION

The Hawkeye 931 and 951 provide accurate load trending information with a

proportional 4-20mA output signal. These devices offer three amperage ranges for

versatility, with easy slide-switch selection. The command relay is fully integrated in

the device, but it is isolated from the current sensor. This combination makes these

products ideal for start/stop control and status monitoring of motors, using one

device instead of two.

APPLICATIONS

●

Load trending

●

Motor control

●

Positive proof of flow

FEATURES

●

Loop-powered analog current sensor with integral start/stop command relay

●

Reduces the number of installed components...saves time and space

●

Self-gripping split-core for fast retrofit installation...no need to remove

conductor

●

One device to install for start/stop & status...reduces installation charges

●

Power the current sensor and receive the 4-20mA signal with only two wires...

fewer wires required than with traditional 3-wire sensors

●

Selectable factory calibrated ranges up to 120A for increased flexibility and

resolution

●

Factory calibrated switch-selectable ranges (30/60/120A) for high resolution and

installation ease

●

No jumpers on unit...reduce installation error

●

Removable mounting bracket for installation flexibility

●

Bracket can be installed in three different configurations...added flexibility

●

Command relay switches up to 5A@250VAC

●

5-year warranty

SENSED AMPS

30/60/120A*

4mA

0A

20mA

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

Load Trending And Control

Relay In One Package

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

Sensor Power

30mA (max.)@12-30VDC

Insulation Class

600VAC RMS

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Accuracy

±2% F.S. from 10% to 100% (selected range)

Response Time

2 sec.

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing

Do not use LED status indicators as evidence of applied voltage

Current Sensors with Relay:

4-20mA Analog Output

Year

Warranty

5

H931

EXAMPLE LINEAR OUTPUT

Scale software as shown

H931 & H951

TM

HQ0001766.C 08131

Advertising