Installation

Install the FL SWITCH SFN… on a clean DIN rail. To avoid

contact resistance use only clean, corrosion-free rails that

meet the EN 50022 standard. End clamps should be

mounted on both sides of the module to stop the modules

from slipping on the rail.

6.1

Assembly

1.

Place the module onto the DIN rail from above. The

upper holding keyway must be hooked onto the top

edge of the DIN rail.

2.

Push the module from the front towards the mounting

surface.

3.

Once the module has been snapped on properly, check

that it is fixed securely on the rail.

6.2

Removal

1.

Insert a suitable tool (e.g., needle-nose pliers) into the

arresting latch and pull it down.

2.

Pull the module slightly away from the mounting

surface.

3.

Lift the module from the rail.

6.3

Power Connection

The switch is designed for SELV and PELV operation at

+24 V DC according to IEC 61140/EN 61140. Only SELV

and PELV according to the defined standards may be used

for supply purposes.

Snapping the switch onto a grounded DIN rail connects it to

the ground potential. In an environment particularly prone to

EMI, noise immunity can be increased by an additional low-

impedance connection to functional earth ground.

Figure 3

FL SWITCH SFN…TX… power connection

CAUTION:

Only qualified personnel may start up and operate

this device. Qualified personnel are persons

authorized to start up, ground and mark devices,

systems, and equipment according to the

standards of safety technology.

NOTE:

The FL SWITCH SFN… module is designed for

SELV and PELV operation according to

IEC 61140/EN 61140.

WARNING:

A.)THIS EQUIPMENT IS SUITABLE FOR USE IN

CLASS I, ZONE 2, GROUPS A, B, C, AND D OR

NON- HAZARDOUS LOCATIONS ONLY.

B.) WARNING - EXPLOSION HAZARD -

SUBSTITUTION OF COMPONENTS MAY

IMPAIR SUITABILITY FOR CLASS I, ZONE 2.

C.) WARNING - EXPLOSION HAZARD - DO

NOT DISCONNECT EQUIPMENT UNLESS

POWER HAS BEEN SWITCHED OFF OR THE

AREA IS KNOWN TO BE NON-HAZARDOUS.

NOTE:

Connect the DIN rail to protective earth ground

using a grounding terminal block. The modules

are grounded when they are snapped onto the

rail. Connect protective earth ground with low

impedance. 1000 Mbps switches have a

protective ground connecting screw on top.