8.3 Calculation of total deviation (similar to

DIN 16086)

T

he total deviation F

total

according to DIN 16086 is the sum of basic

accuracy F

perf

and longterm stability F

stab

. F

total

is also called

maximum practical deviation or utility error.

F

total

= F

perf

+ F

stab

F

perf

= √((F

T

)

2

+ (F

K

l

)

2

)

W

ith analogue output, the error of the current output F

a

is also added.

F

perf

= √((F

T

)

2

+ (F

K

l

)

2

(+ F

a

)

2

)

W

ith:

l

F

total

: T

otal deviation

l

F

perf

: B

asic accuracy

l

F

stab

: L

ong-term drift

l

F

T

: T

emperature coefficient (influence of medium or ambient

temperature)

l

F

K

l

: D

eviation

l

F

a

: E

rror current output

P

ressure measurement in the pipeline 8 bar (800 KPa)

P

roduct temperature 10 °C, reference temperature 20 °C

C

alculation ΔT: ΔT = 20 °C - 10 °C = 10 K

VEGABAR

52

climate compensated, with measuring range 25 bar

C

alculation of the set Turn Down: TD = 25 bar/8 bar, TD = 3.1

Basic accuracy digital output signal in percent:
F

perf

= √((F

T

)

2

+ (F

K

l

)

2

)

F

T

= (0.02 + 0.03

x TD)%/10 K

F

K

l

= (0.05 + 0.025

x TD)%

F

perf

= √((0.02 + 0.03

x 3.1)%/10 K x10 K)

2

+ (0.05 + 0.025

x 3.1)

2

)

F

perf

=

0.17 %

Total deviation digital output signal in percent:
F

total

= F

perf

+ F

stab

F

stab

= (0.1 %

x TD)/year

F

stab

= (0.1 %

x 3.1)/year

F

stab

=

0.31 %

F

total

=

0.17 % + 0.31 % = 0.48 %

Total deviation digital output signal absolute:
F

total

=

0.48 %

x 8 bar/100 % = 38.4 mbar

Total deviation

Example

VEGABAR

52 • 4 … 20

mA/HART - climate compensated

41

8 M