VEGA VEGABAR 82 Profibus PA - Operating Instructions User Manual

Page 40

Advertising
background image

40

6 Set up with the display and adjustment module

VEGABAR 82 • Profibus PA

45031-EN-131107

Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].

Now select with [->] the menu item "Adjustment", then "Min.

adjustment" and confirm with [OK].

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value (e.g. 10 %) with [+] and save

with [OK]. The cursor jumps now to the pressure value.

4. Enter the pressure value corresponding to the min. level (e.g.

0 mbar).

5. Save settings with [OK] and move with [ESC] and [->] to the max.

adjustment.

The min. adjustment is finished.
For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.

Proceed as follows:
1. Select with [->] the menu item "Max. adjustment" and confirm

with [OK].

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value (e.g. 90 %) with [+] and save

with [OK]. The cursor jumps now to the pressure value.

4. Enter the pressure value for the full vessel (e.g. 900 mbar) cor-

responding to the percentage value.

5. Save settings with [OK]
The max. adjustment is finished.
For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. The linearization applies to the measured

value indication and the current output.

Setup - Min. adjustment

Level

Setup - Max. adjustment

Level

Setup - Linearization

Advertising