11 Supplement
VEGABAR 82 • Profibus PA
45031-EN-131107
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … 5 psi
435 psi
0 psi
0 … 15 psi
510 psi
0 psi
0 … 30 psi
725 psi
0 psi
0 … 150 psi
1300 psi
0 psi
0 … 300 psi
1900 psi
0 psi
0 … 900 psi
2900 psi
0 psi
0 … +1450 psig
(only for measuring cell ø 28 mm)
2900 psig
0 psi
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ 1. FB
PV
Ʋ 2. FB
SV 1
Ʋ 3. FB
SV 2
Current value
Ʋ Non-Ex and Ex ia instrument
10 mA, ±0.5 mA
Ʋ Ex-d instruments
16 mA, ±0.5 mA
Resolution, digital
< 1 mm (0.039 in)
Dynamic behaviour output
Run-up time approx.
10 s
Dynamic characteristics, depending on medium, temperature and, if applicable, chemical seal