ACM4 series

Overview:

These units convert one (1) 12 to 24 volt AC or DC input into four (4) independently controlled fused or PTC protected
outputs. These power outputs can be converted to dry form “C” contacts (ACM4 only). Outputs are activated by an open
collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button,
PIR, etc. The units will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes,
Magnetic Door Holders, etc. All interconnecting devices must be UL Listed. Outputs will operate in both Fail-Safe and/
or Fail-Secure modes. Units are designed to be powered by one common power source which will provide power for both
the board operation and locking devices, or two (2) totally independent power sources, one (1) providing power for board
operation and the other for lock/accessory power. The FACP Interface enables Emergency Egress, Alarm Monitoring, or
may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of
the four (4) outputs.

Configuration Reference Chart:

Altronix

Model

Number

Number

of

Outputs

Fuse

Protected

Outputs

PTC

Protected

Outputs

Output

Ratings

Class 2 Rated

Power

Limited

Agency

Listings

UL Listings and

File Numbers

ACM4

4

x

---

3 amp

---

UL File # BP6714

UL Listed for Access Control

System Units (UL 294).

“Signal Equipment” Evaluated to CSA

Standard C22.2 No.205-M1983

ACM4CB

4

---

x

2 amp

x

Specifications:

• 12 to 24volt AC or DC operation (setting not required).
• Input Ratings (ACM4/ACM4CB only):
- 12VDC @ 0.4 amp or 24VDC @ 0.2 amp.
• Power supply input options:
a) One (1) common power input (board and lock power).
b) Two (2) isolated power inputs (one (1) for board power and one (1) for lock/hardware power).
• Four (4) Access Control System trigger inputs:
a) Four (4) normally open (NO) inputs.
b) Four (4) open collector sink inputs.
c) Any combination of the above.
• Four (4) independently controlled outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5 amp rated relay outputs (ACM4 only).
c) Any combination of the above (ACM4 only).
• Four (4) auxiliary power outputs (unswitched).
• Output ratings:
- Fuses are rated 3 amp each.
- PTCs are rated 2.5 amp each.
• Main fuse is rated at 10 amp.

Note: For Models ACM4/ACM4CB refer to the Total Output Chart on Page 2.

Note: Operating temperature range should be 0 to +49

o

C.

• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the four (4) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• FACP output relay (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Removable terminal blocks facilitate ease of installation.
Board Dimensions (approximate): 5.125”L x 3.625”W x 1.25”H (ACM4 and ACM4CB).