Altronix ACM4CB Installation Instructions User Manual

Page 5

Advertising
background image

ACM4 series

- 5 -

LED Diagnostics:

LED

ON

OFF

LED 1 - LED 4 (Red)

Output relay(s) energized.

Output relay(s) de-energized.

TRG (Green)

FACP input triggered (alarm condition).

FACP normal (non-alarm condition).

Terminal Identification Table:

Terminal Legend

Function/Description

-- Power +

12VDC to 24VDC input from UL Listed Access Control Power Supply.

-- Control +

These terminals can be connected to a separate, UL Listed Access Control Power Supply
to provide isolated operating power for the ACM4/ACM4CB
(jumpers J1and J2 Must be removed).

TRIGGER
INPUT 1 - INPUT 4
IN, GND

From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir’s, etc.).

OUTPUT 1 - OUTPUT 4
NC, C, NO, COM

12 to 24 volts AC/DC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(When using AC power supplies polarity need not be observed),
NC, C, NO become form “C” 5 amp 24VAC/VDC rated dry outputs when fuses are
removed (ACM4). Contacts shown in a non-triggered state.

FACP INTERFACE
T, + INPUT --

Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (Fig. 3 through 7, pg. 6).

FACP INTERFACE
NC, C, NO

Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting.
(This output has not been evaluated by UL).