Altronix ACM4CB Installation Instructions User Manual

Page 3

Advertising
background image

ACM4 series

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Product is intended for indoor use only.
1. Refer to Sub Assembly Installation Instruction for mounting Rev. MS042511.
Carefully review:
Typical Application Diagram

(pg. 4)

Terminal Identification Table

(pg. 5)

LED Diagnostics

(pg. 5)

Hook-up Diagrams

(pg. 6)

2.

Power supply input:

The units can be powered with one (1) Listed Access Control Power Supply which will provide power for both
board operation and the locking devices or two (2) separate Listed Access Control Power Supplies, one (1) to provide
power for the board operation and the other to provide power for the locking devices and/or access control hardware.

Note: The input power can be either 12 to 24 volts AC or DC operation.

Input Ratings (ACM4/ACM4CB only):
- 12VDC @ 0.4 amp or 24VDC @ 0.2 amp.
(a) Single power supply input:
If the unit and the locking devices are to be powered using a single Listed Access Control Power Supply, connect
the output (12 to 24 volts AC or DC) to the terminals marked [- Control +].
(b) Dual power supply inputs (Fig. 1, pg. 4):
When the use of two Listed Access Control Power Supplies is desired, jumpers J1 and J2 (located to the left
of the power/control terminals) must be cut. Connect power for the unit to the terminals marked [- Control +]
and connect power for the locking devices to the terminals marked [- Power +].
Note: When using DC Listed Access Control Power Supplies polarity must be observed. When using AC Listed
Access Control Power Supplies polarity need not be observed.

Note: For UL compliance the power supplies must be UL Listed for Access Control Systems and accessories.

3.

Output options (Fig. 1, pg. 4):

The ACM4 will provide either four (4) switched power outputs, four (4) dry form “C” outputs, or any
combination of of both switched power and form “C” outputs, plus four (4) unswitched auxiliary power outputs.
The ACM4CB will provide four (4) switched power outputs or four (4) unswitched auxiliary power outputs.

(a) Switched Power outputs:
Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation
connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation
connect the positive (+) input of the device being powered to the terminal marked [NO].
(b) Form “C” outputs (ACM4):
When form “C” outputs are desired the corresponding output fuse (1-4) must be removed. Connect negative (-) of
the power supply directly to the locking device. Connect the positive (+) of the power supply to the terminal marked
[C]. For Fail-Safe operation connect the positive (+) of the device being powered to the terminal marked NC].
For Fail-Secure operation connect the positive (+) of the device being powered to the terminal marked [NO].
(c) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device
being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.
Note: When wiring for power-limited outputs utilize a knockout separate from the one used for
non power-limited wiring.
4.

Input trigger options (Fig. 1, pg. 4):

(a) Normally Open [NO] input trigger:
Inputs 1-4 are activated by normally open or open collector sink inputs.
Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector output to the terminal marked [IN] and the
common (negative) to the terminal marked [GND].
5.

Fire Alarm Interface options (Figs. 3 through 7, pg. 6):

A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will
trigger selected outputs. To enable FACP Disconnect for an output open the corresponding switch [SW1-SW4].
To disable FACP disconnect for an output close the corresponding switch [SW1-SW4].
(a) Normally Open [NO] input:
For non-latching hook-up (Fig. 4, pg. 6). For latching hook-up (Fig. 5, pg. 6).
(b) Normally Closed [NC] input:
For non-latching hook-up (Fig. 6, pg. 6). For latching hook-up (Fig. 7, pg. 6).

Advertising