EMISSIONS DATA
EPA TIER-3 2005 - ---- *************************************************** D6
Gaseous emissions data measurements are consistent with those described
in 40 CFR, EU 97/68/EC, ECE Regulation No. 96 and ISO 8178 for measuring
HC, CO, PM, and NOx.
Gaseous emissions values are WEIGHTED CYCLE AVERAGES and are in compliance
with the following non-road regulations:
LOCALITY AGENCY/LEVEL MAX LIMITS - g/kW-hr
------------------ ------------ -----------------------------------
U. S. (incl Calif) EPA/TIER-3 CO:3.5 NOx + HC:4.0 PM:0.2
REFERENCE EXHAUST STACK DIAMETER
--
WET EXHAUST MASS
5,665.9 LB/HR
WET EXHAUST FLOW (917.60 F STACK TEMP )
3,337.24 CFM
WET EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )
1,173.00 STD CFM
DRY EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )
1,074.98 STD CFM
FUEL FLOW RATE
28 GAL/HR