Technical data – Milton CAT C18 600 kW 750 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual

Page 4

Advertising
background image

®

STANDBY 600 ekW 750 kVA

60 Hz 1800 rpm 480 Volts

TECHNICAL DATA

Open Generator Set - - 1800 rpm/60 Hz/480 Volts

DM8518

EPA Certified Tier 2

Generator Set Package Performance

Genset Power rating @ 0.8 pf
Genset Power rating with fan

750 kVA
600 ekW

Coolant to aftercooler

Coolant to aftercooler temp max

49 º C

120 º F

Fuel Consumption

100% load with fan
75% load with fan
50% load with fan

161.6 L/hr

42.7 Gal/hr

129.8 L/hr

34.3 Gal/hr

91.7 L/hr

24.2 Gal/hr

Cooling System

1

Air flow restriction (system)
Air flow (max @ rated speed for radiator arrangement)
Engine Coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity

0.12 kPa

0.48 in. water

804 m³/min

28393 cfm

81.8 L

21.6 gal

20.8 L

5.5 gal

61.0 L

16.1 gal

Inlet Air

Combustion air inlet flow rate

47.4 m³/min

1673.9 cfm

Exhaust System

Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)

534.6 º C

994.3 º F

135.4 m³/min

4781.6 cfm

203 mm

8 in

10.0 kPa

40.2 in. water

Heat Rejection

Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator

189 kW

10748 Btu/min

610 kW

34691 Btu/min

145 kW

8246 Btu/min

119 kW

6768 Btu/min

41.0 kW

2331.7 Btu/min

Alternator

2

Motor starting capability @ 30% voltage dip
Frame
Temperature Rise

1633 skVA
LC7024F
150 º C

270 º F

Emissions (Nominal)

3

NOx g/hp-hr
CO g/hp-hr
HC g/hp-hr
PM g/hp-hr

5.84 g/hp-hr
.48 g/hp-hr
.01 g/hp-hr
.035 g/hp-hr

1

For ambient and altitude capabilities consult your Caterpillar dealer. Air flow restriction (system) is added to existing restriction from

factory.

2

Generator temperature rise is based on a 40º C (104º F) ambient per NEMA MG1-32.

3

Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for

measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuel
with 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.

May 06 2009 13:24 PM

4

Advertising