Milton CAT D175-2 175 kW Controller Specifications User Manual

Page 3

Advertising
background image

E M C P 3 . 2
G E N E R A T O R S E T C O N T R O L L E R

LEHE4942-02

3

WARNING/SHUTDOWN INDICATION

●

Overcrank

●

Low Coolant Temperature Warning

●

High Coolant Temperature Warning/Shutdown

●

Low Oil Pressure Warning/Shutdown

●

Overspeed

●

Control Switch Not In Auto

●

High/Low Battery Voltage

●

Emergency Stop Activated

Notes:

●

Warning condition activates common alarm
output signal and common flashing yellow
indicating lamp.

●

Shutdown condition activates common
shutdown output signal and common flashing
red indicating lamp.

●

Warning/Shutdown conditions result in text
message in EMCP 3 display event log.

DIGITAL INPUTS (8 TOTAL)

●

Emergency Stop

●

Remote Start

●

6 Programmable

Digital inputs can be programmed for various
alarm, shutdown, and status conditions including:

●

Low Fuel Level

●

High Fuel Level

●

Fuel Leak Detected

●

High Exhaust Temperature

●

Air Damper Closed

●

Circuit Breaker Open/Closed

●

Low Engine Oil Level

●

Low Coolant Level

●

Low Starting Air Pressure

●

Low/High Ambient Air Temperature

●

Spare Fault #1-6.

Inputs can be programmed for either high or low
activation using programmable Normally Open
or Normally Closed contacts.

Note: The number of programmable Digital Inputs
may vary based on specific package configuration.
Refer to Engine Installation Guide for specific
engine application.

PROTECTIVE RELAYING

●

Generator Over/Under Voltage

●

Generator Over/Under Frequency

●

Generator Overcurrent

RELAY OUTPUTS (8 TOTAL)

●

Starter Motor

●

Fuel Control

●

6 Programmable

Relay outputs can be programmed for various
operating conditions including: Air shut-off, or
pre-lube, Common Alarm, Common Shutdown,
Common Warning, Engine Running, Crank Alert,
& Idle/Rated.
Relays are rated for 2A @ 30 VDC and consist
of 6 Form A (Normally Open) contacts. Two of
the programmable outputs are Form C
(Normally Open & Normally Closed) contacts.

Note: These are only rated for DC.

Note: The number of programmable Relay Outputs
may vary based on specific package configuration.
Refer to Engine Installation Guide for specific
engine application.

DISCRETE OUTPUTS

●

1 Programmable

Discrete output can be programmed for various
operating conditions including: Air shut-off,
pre-lube, Common Alarm, Common Shutdown,
Common Warning, Engine Running, Crank Alert,
& Idle/Rated.
Discrete output can sink up to 300mA
and is suitable for driving relay coils or
incandescent lamps.

SENSOR INPUTS

●

Engine Speed (Magnetic Pick-up)

●

Engine Oil Pressure (0-2 k

Ω resistive sender,

1 or 2-wire) – MUI Engines only

●

Engine Coolant Temperature (0-2 k

Ω resistive

sender, 1 or 2-wire) – MUI Engines only

●

Configurable Input (0-2 k

Ω resistive sender)

(for engine oil temperature, etc)

STANDARD FEATURES (CONT’D)

AVAILABLE LOCAL DISPLAY LANGUAGES

• Arabic

• Italian

• Czech

• Latvian

• Danish

• Lithuanian

• Dutch

• Norwegian

• Estonian

• Polish

• Finnish

• Portuguese

• French

• Russian

• German

• Spanish

• Greek

• Slovak

• Hungarian

• Slovene

• Icelandic

• Swedish
• Turkish

Note: Displays contain 2 languages

(English and Local)

Advertising
This manual is related to the following products: