Milton CAT G70LG 70kW_88kVA Spec Sheet User Manual

Page 3

Advertising
background image

STARTING CAPABILITIES (sKVA)

FUEL

Natural Gas

Propane Vapor

Single-Phase 120/240VAC @1.0pf

64

Amps: 267

67

Amps: 279

Three-Phase 120/208VAC @0.8pf

67

Amps: 232

70

Amps: 243

Three-Phase 120/240VAC @0.8pf

67

Amps: 201

70

Amps: 210

Three-Phase 277/480VAC @0.8pf

67

Amps: 101

70

Amps: 105

Three-Phase 346/600VAC @0.8pf

67

Amps: 81

70

Amps: 84

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

70

59

88

117

147

176

205

44

66

88

110

132

154

Upsize 1

100

79

118

157

197

236

275

59

89

118

148

177

206

Upsize 2*

130

116

174

232

290

348

406

87

131

174

218

261

305

*Brushless excitation only

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

STANDBY

Flow at Rated Power

cfm

213

STANDBY

Rated Engine Speed

rpm

1800

Horsepower at Rated kW***

hp

107

Piston Speed

ft/min

1251

BMEP

psi

118.7

*** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

STANDBY

Exhaust Flow (Rated Output)

cfm (m

3

/min)

679.5 (19.2)

Maximum Recommended Back Pressure

inHg

1.5

Exhaust Temp (Rated Output)

ºF (ºC)

1250 (676.7)

Exhaust Outlet Size (Open Set)

in

2.5"

POWER RATINGS (kW)

Fuel Consumption Rates**

Natural Gas

Propane Vapor

Percent Load

ft

3

/hr

m

3

/hr

Percent Load

ft

3

/hr

gal/hr

m

3

/hr

25%

335

9.5

25%

139

3.8

3.9

50%

550

15.6

50%

228

6.3

6.5

75%

730

20.7

75%

302

8.3

8.5

100%

985

27.9

100%

408

11.2

11.6

** Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.

STANDBY

Air Flow (inlet air combustion and radiator)

ft

3

/min (m

3

/min)

5813 (164.6)

System Coolant Capacity

Gal (Liters)

6.3 (23.9)

Heat Rejection to Coolant

BTU/hr

275,800

Max. Operating Air Temp on Radiator

ºF (ºC)

122 (50)

Max. Ambient Temperature

ºF (ºC)

104 (40)

Maximum Radiator Backpressure

in H

2

O

1.50

3 of 5

G70LG

operating data (60Hz)

G70LG 70kW

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.

Advertising