Technical data, Rating definitions and conditions – Milton CAT G3412 375 kW Continuous 375 kW 60 Hz Spec Sheet User Manual
Page 3

S T A N D B Y
3 7 5
e k W
C O N T I N U O U S
3 7 5
e k W
6 0 H z
3
TECHNICAL DATA
Open Generator Set —
Standby
Continuous
1800 rpm/60 Hz/480 Volts
DM5443
DM5444
Package Performance
Power rating
ekW
375
375
Power rating @ 0.8 PF
kVA
469
469
Aftercooler temperature
Deg C
Deg F
54
130
54
130
Fuel Consumption
100% load with fan
N•m
3
/hr
scf/hr
137
5141
137
5141
75% load with fan
N•m
3
/hr
scf/hr
108
4062
108
4062
50% load with fan
N•m
3
/hr
scf/hr
78
2942
78
2942
Cooling System
Ambient air temperature*
Deg C
Deg F
40
105
40
105
Air flow restriction (system)
kPa
in water
0.12
0.5
0.12
0.5
Air flow (maximum @ rated speed for
standard radiator arrangement)
m
3
/min
cfm
1430
50,491
1429
50,491
Engine coolant capacity with radiator
L
Gal
140
37
140
37
Jacket water outlet temperature
Deg C
Deg F
99
210
99
210
Exhaust System
Combustion air inlet flow rate
N•m
3
/min
scfm
36
1307
36
1307
Exhaust gas stack temperature
Deg C
Deg F
371
700
371
700
Exhaust gas flow rate
N•m
3
/min
cfm
37
3125
37
3125
Exhaust flange size (internal diameter)
mm
in
203
8
203
8
Exhaust system backpressure
(maximum allowable)
kPa
in water
6.7
27
6.7
27
Heat Rejection
Low Heat Value (LHV) fuel input
kW
Btu/min
1386
78,809
1386
78,809
Heat rejection to jacket water
(includes oil cooler)
kW
Btu/min
457
25,983
457
25,983
Total heat rejection to exhaust (LHV to 25° C)
kW
Btu/min
334
19,001
334
19,001
Heat rejection to exhaust (LHV to 120° C)
kW
Btu/min
220
9665
220
9665
Heat rejection to A/C
kW
Btu/min
64
3659
64
3659
Heat rejection to atmosphere from engine
kW
Btu/min
55
3152
55
3152
Heat rejection to atmosphere from generator
kW
Btu/min
29
1660
29
1660
Generator
Motor starting capability @ 30% voltage dip**
kVA
928
928
Frame
592
592
Temperature rise
Deg C
130
105
Emissions***
NOx
g/bhp-hr
2
2
CO g/bhp-hr
1.9
1.9
HC (total)
g/bhp-hr
5.4
5.4
HC (non-methane)
g/bhp-hr
0.81
0.81
Exhaust O
2
(dry)
%
8.7
8.7
**
*Ambient capability at 200 m (660 ft) above sea level. For ambient capability at other altitudes, consult your Caterpillar dealer.
*
**Assumes synchronous driver
***Emissions data measurement is consistent with those described in EPA CFR 40 PART 89 SUBPART D and ISO 8178-1 for
measuring HC, CO, CO
2
and NOx. Data shown is based on steady state engine operating conditions of 77° F, 28.43 inches HG
and fuel having a LHV of 920 BTU per cubic foot at 30.00 inches HG absolute and 32° F. Not to exceed emission data shown is
subject to instrumentation, measurement, facility and engine fuel system adjustments.
Standby — Output available with varying load for the
duration of the interruption of the normal source power.
Continuous — Output available without varying load
for an unlimited time.
Ratings are based on ISO3046/1 standard reference
conditions of 25° C (77° F) and 100 kPa (29.61 in Hg).
Ratings are based on pipeline natural gas having a LHV
(low heat value) of 36.2 mJ/N•m
3
(920 Btu/cu ft). Variations
in altitude, temperature, and gas composition from standard
conditions or the use of a three way catalyst may require
a reduction in engine horsepower.
RATING DEFINITIONS AND CONDITIONS