Technical data – Milton CAT C27 750 kW 938 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual

Page 4

Advertising
background image

®

STANDBY 750 ekW 938 kVA

60 Hz 1800 rpm 480 Volts

TECHNICAL DATA

Open Generator Set - - 1800 rpm/60 Hz/480 Volts

DM9071

EPA Certified Tier 2

Generator Set Package Performance

Genset Power rating @ 0.8 pf
Genset Power rating with fan

937.5 kVA
750 ekW

Coolant to aftercooler temp max

Coolant to aftercooler temp max

49 º C

120 º F

Fuel Consumption

100% load with fan
75% load with fan
50% load with fan

202.6 L/hr

53.5 Gal/hr

162.2 L/hr

42.8 Gal/hr

115.9 L/hr

30.6 Gal/hr

Cooling System

1

Air flow restriction (system)
Air flow (max @ rated speed for radiator arrangement)
Engine Coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity

0.12 kPa

0.48 in. water

1136 m³/min

40117 cfm

160.0 L

42.3 gal

55.0 L

14.5 gal

105.0 L

27.7 gal

Inlet Air

Combustion air inlet flow rate

57.6 m³/min

2034.1 cfm

Exhaust System

Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)

509.9 º C

949.8 º F

159.9 m³/min

5646.8 cfm

203 mm

8 in

10.0 kPa

40.2 in. water

Heat Rejection

Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator

326 kW

18540 Btu/min

715 kW

40662 Btu/min

134 kW

7621 Btu/min

147 kW

8360 Btu/min

34.5 kW

1962.0 Btu/min

Alternator

2

Motor starting capability @ 30% voltage dip
Frame
Temperature Rise

2034 skVA
596
130 º C

234 º F

Lube System

Sump refill with filter

68.0 L

18.0 gal

Emissions (Nominal)

3

NOx g/hp-hr
CO g/hp-hr
HC g/hp-hr
PM g/hp-hr

5.32 g/hp-hr
.24 g/hp-hr
.03 g/hp-hr
.022 g/hp-hr

1

For ambient and altitude capabilities consult your Caterpillar dealer. Air flow restriction (system) is added to existing restriction from

factory.

2

UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator

temperature rise is based on a 40ºC ambient per NEMA MG1-32.

3

Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for

measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuel
with 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.