Rating definitions and conditions – Milton CAT 3516C HD 2500 kW 3125 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual
Page 5

®
STANDBY 2000 ekW 2500 kVA
60 Hz 1800 rpm 480 Volts
RATING DEFINITIONS AND CONDITIONS
Meets or Exceeds International Specifications: ·ABGSM
TM3, AS1359, AS2789, BS4999, BS5000, BS5514,
DIN6271, DIN6280, EGSA101P, IEC34/1, ISO3046/1,
ISO8528, JEM1359, NEMA MG 1-22, VDE0530,
89/392/EEC, 89/336/EEC
Standby - Output available with varying load for the
duration of the interruption of the normal source power.
Standby power in accordance with ISO8528. Fuel stop
power in accordance with ISO3046/1, AS2789, DIN6271,
and BS5514. Standby ambients shown indicate ambient
temperature at 100 percent load which results in a
coolant top tank temperature just below the shutdown
temperature.
Ratings are based on SAE J1995 standard conditions.
These ratings also apply at ISO3046/1, DIN6271, and
BS5514 standard conditions.
Fuel Rates are based on fuel oil of 35º API (16º C or 60º F)
gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
when used at 29º C (85º F) and weighing 838.9 g/liter
(7.001 lbs/U.S. gal.).
Additional Ratings may be available for specific
customer requirements. Consult your Caterpillar
representative for details.