Milton CAT C15 450 ekW 563 kVA 60 Hz 1800 rpm 480 Volts Performance Data User Manual
Page 4

EMISSIONS DATA
EPA TIER-3 2005 - ---- *************************************************** D7
Gaseous emissions data measurements are consistent with those described
in 40 CFR, EU 97/68/EC, ECE Regulation No. 96 and ISO 8178 for measuring
HC, CO, PM, and NOx.
Gaseous emissions values are WEIGHTED CYCLE AVERAGES and are in compliance
with the following non-road regulations:
LOCALITY AGENCY/LEVEL MAX LIMITS - g/kW-hr
------------------ ------------ -----------------------------------
U. S. (incl Calif) EPA/TIER-3 CO:3.5 NOx + HC:4.0 PM:0.2
REFERENCE EXHAUST STACK DIAMETER
--
WET EXHAUST MASS
6,726.3 LB/HR
WET EXHAUST FLOW (917.60 F STACK TEMP )
3,955.25 CFM
WET EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )
1,390.00 STD CFM
DRY EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )
1,273.80 STD CFM
FUEL FLOW RATE
35 GAL/HR
Page 4 of 8
Performance Data
9/21/2009
http://tmiweb.cat.com/tmi/servlet/cat.edis.tmiweb.gui.TMIDirector?Action=buildtab&refki...