Milton CAT C15 Factory Integral Fuel Tank Base User Manual

C15 integral fuel tank base, Features description, Options

Advertising
background image

FEATURES

DESCRIPTION

A T T A C H M E N T S

C15 INTEGRAL
FUEL TANK BASE

Diesel Generator Set
400 – 550 kVA 50 Hz
350 – 550 kW 60 Hz

●

UL 142 listed

●

Designed and built to comply with
NFPA 30, 37, 110

●

Direct reading fuel level gauge

●

Primary tank leak detection switch in
containment basin

●

Fuel fill – 101.6 mm (4 in), lockable cap

●

Supply and return ports equipped with dip tubes

●

Additional capacity at top to contain spillage

●

Additional capacity at bottom to (weather
protective and sound sediment pickup)

●

Internally baffled to separate supply and return
fuel ports

●

Primary tank atmospheric vent – 50.8 mm (2 in)
NPT with cap and screen

●

Interior tank surfaces coated with a solvent-based,
thin-file rust preventative

●

Welded steel containment basin (minimum of
110% of primary tank capacity)

●

Tank designed to contain coolant and engine
oil spills

●

High performance, gloss black, alkyd acrylic
enamel exterior paint over epoxy based primer

●

Heavy

1

⁄

4

" steel construction primary (inner) tank

and side channels

●

Integral diesel fuel tank is incorporated into the
generator set base frame.

●

Robust base design includes linear vibration
isolators between tank base and engine-
generator.

●

Emergency vent on primary and secondary tanks
are sized in accordance with NFPA 30.

●

Dual wall.

●

Primary and secondary tanks are leak tested
at 20.7 kPa (3 psi) minimum.

●

Compatible with enclosures (weather protective
and sound attenuated).

OPTIONS

●

Manual fuel transfer pump

●

Auto fuel transfer system
– Below grade main tank (pumped supply/

gravity return)

– Elevated main tank (gravity supply)
– Pumped supply from free standing

●

Low fuel level switch (alarm/shutdown)

LEHE5511-00