Milton CAT D100-6_S 100 kW Sub Base Tank User Manual

C4.4 and c6.6 sub-base fuel tanks

Advertising
background image

A T T A C H M E N T S

LEHE0406-01 (07/13)

FEATURES

DESCRIPTION

UL listed for the United States UL142 and

•

Canada ULC–S601

Compliant with NFPA 30, 37, and 110 and B139-09

•

standards

Welded heavy steel gauge construction with a

•

containment basin sized as a minimum 110% of

the tank

Gloss black polyester triglycidyl isocyanurate

•

(TGIC) powder coating.

Dedicated external customer interface area with

•

access to the 4” (101.6mm) Fuel fill, visual level

gauge, normal and emergency vents

Rear electrical stub-up area with removable

•

access panel

Removable engine supply and return dip tubes

•

Two additional 1” (25.4mm) ports for customer

•

use

Tanks are rated to safely support the weight of

•

the generator

8 gal (30.3L) drip pan for oil and coolant (for

•

generator sets up to 60ekW only)

Standard NPT tank fittings

•

UL listed emergency vents sized as per UL

•

Standards 3” (76.2mm), 4” (101.6mm) and 5”

(127mm) NPT

Normal atmospheric vent 1-1/4” (31.75mm)

•

Top mounted fuel level sender with control panel

•

alarms

Top mounted leak detection switch

•

Lockable fuel fill cap, 4” (101.6mm) NPT

•

Dual wall, secondary containment

•

Pressure tested to UL requirements

•

Fuel tank mounts directly below generator Skid

•

Base

Modular tank design is compatible with all

•

factory units Open and Enclosed.

OPTIONS

Emergency vent and normal vent extension kits

•

12 ft (3.66m)

5 gal (18.9 L ) spill containment

•

Overfill prevention valve

•

Tank riser to allow for visual secondary

•

containment leak inspection

C4.4 and C6.6
Sub-Base Fuel Tanks

Newberry

Diesel Generator Set

40 – 175 kW 60 Hz

Image shown may not reflect actual package.

Advertising