Milton CAT G60LG 60kW_75kVA Spec Sheet User Manual

Page 3

Advertising
background image

STARTING CAPABILITIES (sKVA)

FUEL

Natural Gas

Propane Vapor

Single-Phase 120/240VAC @1.0pf

60

Amps: 250

60

Amps: 250

Three-Phase 120/208VAC @0.8pf

60

Amps: 208

60

Amps: 208

Three-Phase 120/240VAC @0.8pf

60

Amps: 180

60

Amps: 180

Three-Phase 277/480VAC @0.8pf

60

Amps: 90

60

Amps: 90

Three-Phase 346/600VAC @0.8pf

60

Amps: 72

60

Amps: 72

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

60

42

63

83

104

125

146

32

47

62

78

94

110

Upsize 1

70

59

88

117

147

176

205

44

66

88

110

132

154

Upsize 2

100

79

118

157

197

236

275

59

89

118

148

177

206

Upsize 3*

130

116

174

232

290

348

406

87

131

174

218

261

305

*Brushless excitation only

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

STANDBY

Flow at Rated Power

cfm

185

STANDBY

Rated Engine Speed

rpm

1800

Horsepower at Rated kW***

hp

96

Piston Speed

ft/min

1251

BMEP

psi

101.8

*** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

STANDBY

Exhaust Flow (Rated Output)

cfm (m

3

/min)

520 (14.7)

Maximum Recommended Back Pressure

inHg

1.5

Exhaust Temp (Rated Output)

ºF (ºC)

1050 (565.6)

Exhaust Outlet Size (Open Set)

in

2.5"

POWER RATINGS (kW)

Fuel Consumption Rates**

Natural Gas

Propane Vapor

Percent Load

ft

3

/hr

m

3

/hr

Percent Load

ft

3

/hr

gal/hr

m

3

/hr

25%

310

8.8

25%

128

3.5

3.6

50%

500

14.2

50%

207

5.7

5.9

75%

665

18.8

75%

275

7.6

7.8

100%

900

25.4

100%

373

10.3

10.6

** Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.

STANDBY

Air Flow (inlet air combustion and radiator)

ft

3

/min (m

3

/min)

5785 (163.8)

System Coolant Capacity

Gal (Liters)

6.3 (23.9)

Heat Rejection to Coolant

BTU/hr

252,000

Max. Operating Air Temp on Radiator

ºF (ºC)

122 (50)

Max. Ambient Temperature

ºF (ºC)

104 (40)

Maximum Radiator Backpressure

in H

2

O

1.50

3 of 5

G60LG

operating data (60Hz)

G60LG 60kW

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.