Milton CAT G60LG 60kW_75kVA Spec Sheet User Manual
Page 3

STARTING CAPABILITIES (sKVA)
FUEL
Natural Gas
Propane Vapor
Single-Phase 120/240VAC @1.0pf
60
Amps: 250
60
Amps: 250
Three-Phase 120/208VAC @0.8pf
60
Amps: 208
60
Amps: 208
Three-Phase 120/240VAC @0.8pf
60
Amps: 180
60
Amps: 180
Three-Phase 277/480VAC @0.8pf
60
Amps: 90
60
Amps: 90
Three-Phase 346/600VAC @0.8pf
60
Amps: 72
60
Amps: 72
sKVA vs. Voltage Dip
480VAC
208/240VAC
Alternator
kW
10%
15%
20%
25%
30%
35%
10%
15%
20%
25%
30%
35%
Standard
60
42
63
83
104
125
146
32
47
62
78
94
110
Upsize 1
70
59
88
117
147
176
205
44
66
88
110
132
154
Upsize 2
100
79
118
157
197
236
275
59
89
118
148
177
206
Upsize 3*
130
116
174
232
290
348
406
87
131
174
218
261
305
*Brushless excitation only
COOLING
COMBUSTION AIR REQUIREMENTS
ENGINE
EXHAUST
STANDBY
Flow at Rated Power
cfm
185
STANDBY
Rated Engine Speed
rpm
1800
Horsepower at Rated kW***
hp
96
Piston Speed
ft/min
1251
BMEP
psi
101.8
*** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
STANDBY
Exhaust Flow (Rated Output)
cfm (m
3
/min)
520 (14.7)
Maximum Recommended Back Pressure
inHg
1.5
Exhaust Temp (Rated Output)
ºF (ºC)
1050 (565.6)
Exhaust Outlet Size (Open Set)
in
2.5"
POWER RATINGS (kW)
Fuel Consumption Rates**
Natural Gas
Propane Vapor
Percent Load
ft
3
/hr
m
3
/hr
Percent Load
ft
3
/hr
gal/hr
m
3
/hr
25%
310
8.8
25%
128
3.5
3.6
50%
500
14.2
50%
207
5.7
5.9
75%
665
18.8
75%
275
7.6
7.8
100%
900
25.4
100%
373
10.3
10.6
** Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.
STANDBY
Air Flow (inlet air combustion and radiator)
ft
3
/min (m
3
/min)
5785 (163.8)
System Coolant Capacity
Gal (Liters)
6.3 (23.9)
Heat Rejection to Coolant
BTU/hr
252,000
Max. Operating Air Temp on Radiator
ºF (ºC)
122 (50)
Max. Ambient Temperature
ºF (ºC)
104 (40)
Maximum Radiator Backpressure
in H
2
O
1.50
3 of 5
G60LG
operating data (60Hz)
G60LG 60kW
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.