8 $aa6 – B&B Electronics I-7060 - Manual User Manual
Page 37
Advertising

37
I-7000 DIO Manual
Rev:B1.2
2.8 $AA6
Description : Read Digital I/O Status
Command : $AA6[CHK](cr)
$
delimiter character
AA
address of reading module (00 to FF)
6
command for read digital input/output status
Response : Valid Command :
!(Data)[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no
response.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
(Data) digital input/output value (Ref Sec.1.9)
Example :
Command : $016
Receive : !0F0000
Assume module is I-7060, read address 01 DIO status, return
0F00, digital input IN1 to IN4 are open, digital output RL1 to
RL4 are off.
Related Command :
Sec.2.14 @AA
Related Topics :
Sec1.9 Configuration Tables
Advertising