22 ~aa4v – B&B Electronics I-7060 - Manual User Manual
Page 53

53
I-7000 DIO Manual
Rev:B1.2
2.22 ~AA4V
Description : Read PowerOn/Safe Value.
Command : ~AA4V[CHK](cr)
~
delimiter character
AA
address of reading module (00 to FF)
4
command for read PowerOn/Safe value
V
P = read PowerOn value, S = read Safe value
Response : Valid Command :
!AA(Data)[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no
response.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
(Data) PowerOn Value or Safe Value
For I-7042/42D/43/43D (Data) is VVVV, where VVVV
is the PowerOn Value (or Safe Value).
For other modules, (Data) is VV00, where VV is the
PowerOn Value(or Safe Value).
Example :
Command : @010000
Receive : >
Output address 01 value 0000, return success.
Command : ~015S
Receive : !01
Set address 01 Safe Value, return success.
Command : @01FFFF
Receive : >
Output address 01 value FFFF, return success.