5.2.5 S7 Current Limit in traveling movement application
The frequency converter limits the maximum current. The limit settings for different currents are shown in the
following table. The limit is a percentage of the device’s nominal current.
Frequency converter
model
Nominal current [A]
003
2.4
006
5.6
Switch S7
Current
Limit [%]
003 [A]
006
[A]
Motor Example
-1
-2
-3
003
006
0
1
0
150 % (*)
3.6
7.7
2 x MF06MA200
2 x MF06LA200,
2 x MF06LA100,
4 x MF06MA200
1
1
1
130 %
3.1
6.6
1
1
0
120 %
2.9
6.1
0
0
0
110 %
2.6
5.6
MF06LA200
1
0
1
100 %
2.4
5.1
0
0
1
90 %
2.2
4.6
MF06MA200
2 x MF06MA200,
MF06LA200, MF06LA100
1
0
0
80 %
1.9
4.1
0
1
1
70 %
1.7
3.6
MF06MK200 35Hz
MF06MA200
(*) Factory default setting.