C.7 serial communication troubleshooting – SENA PS400 User Manual

Page 68

Advertising
background image

68

The HelloDevice Pro
Series is configured to
reject IP address of the
PC

Change the remote host access control parameter using serial
or remote console to allow the IP address of the PC

TCP connection with
the other host is
established already

Close established TCP connection or connect later

C.7 Serial communication troubleshooting

Problem

Cause

Action

Serial data are not
transferred by
TCP/IP immediately

Too large inter-character
timeout

Set inter-character timeout with smaller value

Cannot
communicate with
the HelloDevice Pro
Series

Invalid serial port
configuration

Check if serial port configuration of the HelloDevice Pro Series
are the same with that of the serial device

Only serial port#2
of PS400 is not
working (PS400
only)

Serial console is used

Serial port#2 of the PS400 is used commonly for both data port
and serial console port. While serial console is used, data
transfer through serial port#2 is disabled. Close serial console to
use serial port#2 for data transfer.

Invalid data
transferred

Invalid serial port
configuration

Check if serial port configuration is correct.

Invalid serial port
configuration

Check if serial port is set to RS485 Echo or RS485 Non-echo
mode.

RS485 mode is not
working

Terminator resistor is not
attached

The HelloDevice Pro Series has no terminator resistor inside for
RS485 communication. Please attach a 120

resistor between

Data+ and Data- pins.

Invalid serial port
configuration

Check if serial port is set to RS422 mode.

RS422 mode is not
working

Terminator resistor is not
attached

The HelloDevice Pro Series has no terminator resistor inside for
RS422 communication. Please attach 120

resistors between

Tx+, Tx- and between Rx+, Rx- pins.