Configuration – QTech Data Systems DNP3 RTU User Manual

Page 24

Advertising
background image

DATRAN XL4 RTU – Owners Manual – v1.1 June 2012

www.qtech.co.nz

Page 24

CONFIGURATION

CONFIGURATION

CONFIGURATION

CONFIGURATION JUMPERS

JUMPERS

JUMPERS

JUMPERS

This section describes how to configure the Q22 I/O board via the various on-board configuration jumpers.

The power should be removed from the module by removing the power connector before carrying
out any of the configurations detailed below.

The Q22 Module incorporates static discharge sensitive devices. Normal Anti Static Discharge
precautions should be employed when setting up and making any adjustments to the module.

An anti-static wristband should be worn and the earth connection of this wristband should be

connected to the terminal marked ‘EARTH’ on the Q22 I/O board before any adjustments are made.

Configuration Jumper Functions

Configuration Jumper Functions

Configuration Jumper Functions

Configuration Jumper Functions

The following list describes the function of each of the configuration jumpers on the Q22 I/O board:

J1

This jumper selects the output voltage range for Analog output channel No. 6. Close is 0 to 5V/0 to 20mA
output range whilst open is 0 to 10V output range.

J2

This jumper selects the output voltage range for Analog output channel No 5. Close is 0 to 5V/0 to 20mA
output range whilst open is 0 to 10V output range.

J3

This 2 way jumper selects the output mode of Analog output channel No 6. Pins 1 & 2 closed is current
output mode whilst 2 & 3 closed is voltage output mode.

J4

This 2 way jumper selects the output mode of Analog output channel No 5. Pins 1 & 2 closed is current
output mode whilst 2 & 3 closed is the voltage output mode.

J5

This 2 way jumper selects the single ended input range of Analog input channel No. 2. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.

J6

This 2 way jumper selects the single ended input mode of Analog input channel No. 2. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.

J7

This 2 way jumper selects the single ended input range of Analog input channel No. 1. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.

J8

This 2 way jumper selects the single ended input mode of Analog input channel No. 1. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.

J9

This 2 way jumper selects the single ended input range of Analog input channel No. 3. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.

J10

This 2 way jumper selects the single ended input mode of Analog input channel No. 3. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.

J11

This 2 way jumper selects the single ended input range of Analog input channel No. 4. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.

J12

This 2 way jumper selects the single ended input mode of Analog input channel No. 4. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.

J13

This 2 way jumper selects the single ended input range of Analog input channel No. 5. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.

J14

This 2 way jumper selects the single ended input mode of Analog input channel No. 5. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.

J15

This 2 way jumper selects the single ended input range of Analog input channel No. 6. Pins 1 & 2 closed is
0 to 10V input range, whilst 2 & 3 closed is 0 to 5V/0 to 20mA input range.

J16

This 2 way jumper selects the single ended input mode of Analog input channel No. 6. Pins 1 & 2 closed is
0 to 20mA input mode, 2 & 3 closed is 0 to 10V input mode, whilst jumper open is 0 to 5V input mode.

J17

This 2 way jumper selects the input mode of Analog input channels No’s 1 & 2. Pins 1 & 2 closed is one
differential input channel. Pins 2 & 3 closed is two single ended input channels.

J18

This 2 way jumper selects the input mode of Analog input channels No’s 3 & 4. Pins 1 & 2 closed is one
differential input channel. Pins 2 & 3 closed is two single ended input channels.

Advertising