Accumulator board connections – GE Industrial Solutions GE Zenith Series DPB User Manual
Page 54
Advertising
46
Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
5 4 3 2 1
5 4 3 2 1
J6
J5
Figure 43 - End Feed Accumulator Board
Series DPB Busway Installation & Operation Manual
ACCUMULATOR BOARD CONNECTIONS
MODBUS CONNECTION
Upstream connections (connects to customer’s Building Monitoring System). See Figure 43 - End Feed Accumulator Board.
a. Transmit + is J5 OR J6 pin 1
b. Transmit - is J5 OR J6 pin 2
c. Receive + is J5 OR J6 pin 3
d. Receive - is J5 OR J6 pin 4
e. Ground is J5 OR J6 pin 5
J11
J10
J9
J8
J7
Advertising