Series DPB Busway Installation & Operation Manual

The following Zero Current Registers set a bit for every channel, which reads a current that has gone to zero�
All alarms are active until reset by the controller, or the current returns to the channel� To reset any alarm,
read the register and then write the register with the desired alarm bit cleared�

Note: Current Loss is when the current goes above 1�5 Amps and then goes to zero an alarm is set for that
branch breaker� If bit 15 on the Current Option Setting is set the alarm will be active on the loss of current�

69�

R/W

NV

Zero

Current

Register

bit

0:

Breaker

1A

bit

1:

Breaker

1B

bit

2:

Breaker

1C

bit

3:

Breaker

2A

bit

4:

Breaker

2B

bit

5:

Breaker

2C

bits 6 – 15: Not Used Always read as 0

The following Warning Register sets a bit for every channel, which reads a current above the Warning
Threshold for at least the Warning Time-Delay� All warnings are latching and must be reset by the controller�
To reset any alarm, read the register and the write the register with the desired alarm bit cleared�

70�

R/W

NV

Warning

Register

(Latching)

bit

0:

Breaker

1A

bit

1:

Breaker

1B

bit

2:

Breaker

1C

bit

3:

Breaker

2A

bit

4:

Breaker

2B

bit

5:

Breaker

2C

bits 6 – 15: Not Used Always read as 0

The following Alarm Register sets a bit for every channel, which reads a current above the Alarm Threshold for
at least the Alarm Time-Delay� All alarms are latching and must be reset by the controller� To reset any alarm,
read the register and then write the register with the desired alarm bit cleared�

71�

R/W

NV

Alarm

Register

(Latching)

bit

0:

Breaker

1A

bit

1:

Breaker

1B

bit

2:

Breaker

1C

bit

3:

Breaker

2A

bit

4:

Breaker

2B

bit

5:

Breaker

2C

bits 6 – 15: Not Used Always read as 0

The following Warning Threshold register sets the thresholds for the Warning alarms� A Warning alarm
is given in percent of the breaker size registers for each phase (75 = 75%)� A Warning alarm will occur if
the measured current is above the Warning Threshold for at least the Warning Time Delay� Default for the
Warning thresholds is 70%� The Values that are written to the Warning Threshold must be between 40 and
100 and always below the corresponding Alarm Threshold�

72�

R/W

NV

Warning

Threshold

The following Alarm Threshold registers set the thresholds for the Alarms� A Alarm Threshold register
is given in percent of the breaker size registers for each phase (85 = 85%)� An Alarm will occur if the

Series