Test configurations, Design considerations, Safety considerations – GE Industrial Solutions EVW010A0B Series (Eighth-Brick) User Manual
Page 6: Input filtering, Lineage power 6, Figure 8. output ripple and noise test setup, Figure 9. output voltage and efficiency test setup, Pin and one v
Data Sheet
September 4, 2013
EVW010A0B Series Power Modules
36 – 75Vdc Input; 12.0Vdc Output; 10A Output Current
LINEAGE
POWER
6
Test Configurations
TO OSCILLOSCOPE
CURRENT PROBE
L
TES T
12μH
BA
T
T
ER
Y
C
S
220μF
E.S.R.<0.1
@ 20°C 100kHz
33-100μF
Vin+
Vin-
NOTE: Measure input reflected ripple current with a simulated
source inductance (L
TEST
) of 12μH. Capacitor C
S
offsets
possible battery impedance. Measure current as shown 
above. 
Figure 7. Input Reflected Ripple Current Test 
Setup. 
NOTE: All voltage measurements to be taken at the module
terminals, as shown above. If sockets are used then 
Kelvin connections are required at the module terminals 
to avoid measurement errors due to socket contact 
resistance. 
V
O
(+)
V
O
(
–
)
RESISTIVE
LOAD
SCOPE
COPPER STRIP
GROUND PLANE
10uF
1uF
Figure 8. Output Ripple and Noise Test Setup.
Vout+
Vout-
Vin+
Vin-
R
LOAD
R
contact
R
distribution
R
contact
R
distribution
R
contact
R
contact
R
distribution
R
distribution
V
IN
V
O
NOTE: All voltage measurements to be taken at the module
terminals, as shown above. If sockets are used then 
Kelvin connections are required at the module terminals 
to avoid measurement errors due to socket contact 
resistance. 
Figure 9. Output Voltage and Efficiency Test 
Setup.
 =
V
O
. I
O
V
IN
. I
IN
x
100
%
Efficiency
Design Considerations
Input Filtering
The power module should be connected to a low 
ac-impedance source. Highly inductive source 
impedance can affect the stability of the power 
module. For the test configuration in Figure 7 a 33-
100μF electrolytic capacitor (ESR<0.1
 at 100kHz),
mounted close to the power module helps ensure the 
stability of the unit. Consult the factory for further 
application guidelines. 
Safety Considerations
For safety-agency approval of the system in which the 
power module is used, the power module must be 
installed in compliance with the spacing and 
separation requirements of the end-use safety agency 
standard, i.e., UL 60950-1-3, CSA C22.2 No. 60950-
00, and VDE 0805:2001-12 (IEC60950-1). 
If the input source is non-SELV (ELV or a hazardous 
voltage greater than 60 Vdc and less than or equal to 
75Vdc), for the module’s output to be considered as 
meeting the requirements for safety extra-low voltage 
(SELV), all of the following must be true: 
The input source is to be provided with reinforced
insulation from any other hazardous voltages, 
including the ac mains. 
One V
IN
pin and one V
OUT
pin are to be
grounded, or both the input and output pins are 
to be kept floating. 
The input pins of the module are not operator
accessible.
Another SELV reliability test is conducted on the
whole system (combination of supply source and 
subject module), as required by the safety 
agencies, to verify that under a single fault, 
hazardous voltages do not appear at the 
module’s output. 
Note:
Do not ground either of the input pins of the
module without grounding one of the output 
pins. This may allow a non-SELV voltage to 
appear between the output pins and ground. 
The power module has extra-low voltage (ELV) 
outputs when all inputs are ELV. 
All flammable materials used in the manufacturing of 
these modules are rated 94V-0, or tested to the 
UL60950 A.2 for reduced thickness. 
For input voltages exceeding –60 Vdc but less than or 
equal to –75 Vdc, these converters have been 
evaluated to the applicable requirements of BASIC 
INSULATION between secondary DC MAINS 
DISTRIBUTION input (classified as TNV-2 in Europe) 
and unearthed SELV outputs. 
The input to these units is to be provided with a 
maximum 8 A time-delay fuse in the ungrounded lead.