Post installation procedures, A - 13 – GE Industrial Solutions Galaxy Vector Controller GCM3 User Manual
Page 91
Advertising
Galaxy Vector Controller GCM2, GCM3
Issue 4 January 2008
Communications Appendix A - 13
then the configuration procedure must be repeated.
Post Installation
Procedures
Once configuration has been completed
1. Disconnect the serial cable from the Galaxy Gateway (J2
connector).
2. Connect the 9-pin male end of the auxiliary port cable
assembly to the J2 connector on the Galaxy Gateway.
3. Press SW1 (uP reset) on the Galaxy Gateway.
4. After approximately one minute, observe the LEDs on the
Galaxy Gateway.
• Yellow STATUS LED: OFF
• Green STATUS LED: ON
• Link LED: ON
• XMIT/RCV: May be blinking
The Galaxy Gateway should be communicating over the
network.
5. Secure the cable to the lance on the mounting bracket using
the cable tie provided.