Galaxy Vector Controller GCM2, GCM3

Issue 4 January 2008

T1.317 Objects and Attributes Appendix B - 3

Table B-5: Rectifiers (xx is 01 to 24)

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

gxx,stt

Individual rectifier state

√

√

text

"ON","OFF","STANDBY",

"VACANT"

gxx,adc

Individual rectifier current

√

number

ddd

Table B-6: Battery Reserve Management

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

br1,cle

Batt recharge current limit

enable

√

√

number

0:disable 1:enable

br1,clt

Battery recharge current limit

√

√

number

10-1000 A

br1,btc

Battery test class

√

√

text

"FLOODED","VALVE-REG"

br1,bte

Battery test enable

√

√

number

0:disable 1:enable

br1,btr

Battery test results

√

mixed

result, reserve, load

code: ok, aborted, failed, not run,

interrupted

reserve: dd.d (hours)

load: dddd (amps)

br1,bts

Battery test state

√

√

number

0:inactive 1:active

Table B-7: Battery Sections

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

b01,adc

Battery section 1 current

√

dddd A

b02,adc

Battery section 2 current

√

dddd A

Table B-8: Controller Battery Temperature Channels

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

ct1,val

Controller battery temp chan 1

√

dd °C

ct2,val

Controller battery temp chan 2

√

dd °C

ct3,val

Controller battery temp chan 3

√

dd °C

ct4,val

Controller battery temp chan 4

√

dd °C