minimal time delay of 10 seconds is necessary by the operator prior to closing
the remote bypass contacts and bypassing the drive. DO NOT jumper CTB-8
and CTB-9 together.
PTB101 through PTB102
Dynamic braking chopper option. Provision is made for 10% torque duty of
Repetitive braking in enclosed panel. With Disconnector combination, Cables
are brought from Drive terminal 81 & 82 to the external power terminal board
for all ratings. Similarly for Breaker combination, Panel with 208V up to 10HP,
460V and 575V up to 25HP, Cables are brought from Drive terminal 81 & 82 to
the external power terminal board.
Note: Dynamic Braking Resistors are not provided with the panel.
DEH40652
– Page 10
AN 11-2021 Rev 06, 12/16/2011
CAUTION: Jumpering CTB1-35 and CTB1-36 together will not allow for motor
flux to decay prior to applying AC line power to the motor in the event of a drive
fault. The absence of the 10-second time delay can result in a devastating
torque pulse which can damage your motor, driven load and/or installation. The
AF 650 GP & Bypass panel does not have a line synchronizing function to
permit a smooth switchover to AC line power, therefore a time delay is the only
way to ensure a safe transition.