GE Industrial Solutions AF-650 GP Drive Panel User Manual
Page 51
51
Table – 3 (575V)
Device
AF - 600 Hp
Rating(s)
Minimum Wire
Size
Maximum Wire
Size
Required Torque
NON FUSED DISCONNECTOR
AND FUSE BLOCK
1 through 10
# 14 AWG
# 4 AWG
Note 1
15 through 40
# 14 AWG
# 4 AWG
Note 1
50 through 60
# 8 AWG
1/0
Note 1
75 through 100
# 8 AWG
1/0
Note 1
FUSED DISCONNECTOR
1 through 40
# 10 AWG
# 3 AWG
Note 1
50 through 60
# 14 AWG
# 2/0 AWG
Note 1
75 through 125
# 6 AWG
# 3/0 AWG
Note 1
150 through 300
# 2 AWG
600MCM
Note 1
350 through 600
2 X # 2 AWG
2 X 600MCM
Note 1
Circuit Breaker
1 through 75
# 12 AWG
# 3/0 AWG
Note 1
100 through 200
# 8 AWG
350 MCM
Note 1
250 through 400
2 X 2/0
2 X 500 MCM
Note 1
250 through 400
#8 AWG
600 MCM
Note 1
500 through 600
3X #3/0 AWG
3X 500 MCM
Note 1
Overload Relay
2 through 25
# 14 AWG
# 8 AWG
20 lb. in.
30 through 75
# 10 AWG
# 3 AWG
50 lb. in.
100
# 6 AWG
250 MCM
275 lb. in.
Drive output power Terminal
Board
1 through 10
# 24 AWG
# 10 AWG
5.3 lb.in.
15 through 20
# 6 AWG
# 6 AWG
16 lb.in.
25 through 40
#2 AWG
#2 AWG
40 lb.in.
50 through 60
#1 AWG
#1 AWG
89 lb.in.
75
4/0
4/0
212 lb.in.
100
300MCM
300MCM
212 lb.in.
125 through 150
2 x 2/0
2 x 2/0
Note1, 2
200 through 350
2 x 350MCM
2 x 350MCM
Note1, 2
400 through 600
4 x 500MCM
4 x 500MCM
Note1, 2
Continued…
DEH40653
– Page 5
AN 12-1007 Rev 05, 04/04/2012