3 Safety

Safety Statements

Please read and follow all safety instructions and warnings before installing, maintaining, or
repairing the CPS6000-M2 System:

The CE Mark demonstrates compliance with the European Union Council Directives for
Low Voltage and EMC.

The CPS6000-M2 platform is Underwriters Laboratories (UL) Listed per Subject Letter
1801, DC Power Distribution Centers for Telecommunications Equipment.

CPS6000-M2 shelves equipped with QS820A ringers have hazardous secondary voltages
on the secondary bus output connectors.

Install only in restricted access areas (dedicated equipment rooms, equipment closets, or the
like) in accordance with articles 110-16, 110-17, and 110-18 of the U.S. National Electric
Code (NEC), ANSI/NFPA No. 70, and pursuant to applicable local codes.

This equipment is to be used in controlled environments (an area where the humidity is
maintained at levels that cannot cause condensation on the equipment, the contaminating
dust is controlled, and the steady-state ambient temperature is within the range specified).

This equipment has been evaluated for continuous use in ambient temperature from -40°C
to 65°C.

This equipment must not be installed over combustible surfaces.

For installations in the United States, Listed compression connectors are to be used to
terminate Listed field-wired conductors where required. For all installations, the
appropriate connector is to be applied only to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer's recommended tooling or
tooling approved for that connector.

If the proper connector for the country of installation is not provided, obtain appropriate
connectors and follow manufacturer’s and all local requirements for proper connections.
All national and local rules and regulations should be followed when making field
connections.

The main output voltage (48V) meets SELV requirements.

Insulation on field-wired conductors should be rated no less than 90° Celsius. Wire
conductor size should be sized per electrical codes for 75° Celsius wire, and based on the
ampacity of the associated protection device. Wiring internal to enclosed equipment
cabinets should be rated at 105° Celsius (minimum).