GE Industrial Solutions CPS6000-M2 User Manual
Page 97
CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
97
Controller
Status Display
Power
Unit
LEDs
Dist.
Module
LED
Possible
Problem(s)
Possible Solution(s)
(one
rectifier)
• Rectifier lost
communicati
on with
controller.
1. Reset the rectifier by
removing the rectifier,
waiting approximately
30 seconds, and
replacing.
2. If problem persists,
replace the rectifier.
3. If problem still persists,
call your local field
representative.
MIN Minor
Communication
Fail
• Rectifier
removed
from a
running
system, but
not
uninstalled.
1. Issue the “uninstall
equipment” under the
operations menu for any
rectifier that was
removed.
MAJ Major
Communication
Fail
• LVD Board
lost
communicati
on with the
controller.
1. Replace Distribution
Module Board.
2. If problem persists, call
your local field
representative.
MIN Clock
Battery Low
• Internal
Lithium
Battery Is
Low
1. The battery is not field
replaceable. The
controller unit must be
replaced.
2. Off-load all desired
information such as
alarm history, statistics,
and any field
configuration that is
different than the
standard.
3. Replace controller, and
upload any non-standard
configuration.