1-20 Motor Power [kW]/[HP] (P

m.n

)

Option:

Function:

Enter motor power from nameplate data.

Two sizes down, one size up from nominal AF-60 LP

റ rating.

[1]

0.09 kW/0.12 HP

[2]

0.12 kW/0.16 HP

[3]

0.18kW/0.25 HP

[4]

0.25 kW/0.33 HP

[5]

0.37kW/0.50 HP

[6]

0.55 kW/0.75 HP

[7]

0.75 kW/1.00 HP

[8]

1.10 kW/1.50 HP

[9]

1.50 kW/2.00 HP

[10]

2.20 kW/3.00 HP

[11]

3.00 kW/4.00 HP

[12]

3.70 kW/5.00 HP

[13]

4.00 kW/5.40 HP

[14]

5.50 kW/7.50 HP

[15]

7.50 kW/10.0 HP

[16]

11.00 kW/15.00 HP

NB!

Changing this parameter affects par. 1-22 to 1-25, 1-30, 1-33 and 1-35.

1-22 Motor Voltage (U

m.n

)

Range:

Function:

230/400 V [50 - 999 V]

Enter motor voltage from nameplate data.

1-23 Motor Frequency (f

m.n

)

Range:

Function:

60 Hz

*

[20-400 Hz]

Enter motor frequency from nameplate data.

1-24 Motor Current (I

m.n

)

Range:

Function:

M-type dependent

*

[0.01 - 26.00 A]

Enter motor current from nameplate data.

1-25 Motor Nominal Speed (n

m.n

)

Range:

Function:

M-type Dependent

*

[100 - 9999 RPM] Enter motor nominal speed from nameplate data.

1-29 Auto Tune

Option:

Function:

Use Auto Tune to optimize motor performance.

NB!

This parameter cannot be changed while motor runs.

1.

Stop the frequency converter – make sure motor is at standstill

2.

Choose [2] Enable Auto Tune

3.

Apply start signal

– Via Keypad: Press Hand

AF-60 LP™ Micro Drive Programming Guide