Event registers, Smr2 modbus user manual – GE Industrial Solutions Record Plus FG600 SMR2 Modbus User Manual

Page 16

Advertising
background image

SMR2 Modbus User Manual

13

3029

Flag Cleared Byte

00 &
0xFF

Normal
mode - RO

00 Cleared (trip history can

not be shown on Flag

Module LEDs)

0xFFFF

Not Cleared (trip history can

be shown on Flag Module

LEDs)

3030

Test Kit Modbus Address

0 - 255

Normal

mode - RO

This is to test COMM

switches.

This returns the cumulative

Modbus address set through
two COMM switches.

3031

Test Kit Baud Rate

0 - 3

Normal

mode – RO

00 – 2400

01 – 4800

02 – 9600
03 – 19200

This is to test DIP switches.

3032

Ammeter Display Current

0 - 9999

Test mode

RW

Normal

mode - RO

This holds the value which is

displayed on LCD display
Value greater than 9999 will

be displayed as “----“

Test mode
RW


3033


Ammeter Display Current

Pushbutton


0 - 9999

Normal

mode - RO


Alternate value, which can be

written while testing

Ammeter module. As long as

Select_Phase is pushed, this

value gets displayed.

Value greater than 9999 will
be displayed as “----“



Event Registers

The trip unit stores up to eight events, with each event

utilizing 8 registers to describe the details of the event.

Last eight events are stored in chronological order, with

EVENT 1 being the oldest event and EVENT n being

the newest. An event is automatically cleared once read
by the host.