Interpretation of event codes, Smr2 modbus user manual – GE Industrial Solutions Record Plus FG600 SMR2 Modbus User Manual
Page 18
![background image](/manuals/295292/18/background.png)
SMR2 Modbus User Manual
15
Interpretation of Event Codes
The following table describes the meaning of each
event code
Event
Code
(Hex
)
Meaning
Register 1
Register 2
Register 3
1
Long Time Over-
current Trip
Fault
SOS
Current
Fault SOS Current
2
Short Time O/C trip
Fault SOS
Current
Fault SOS Current
3 Instantaneous
O/C
Trip
Instantaneous
Fault Current
Instantaneous Fault
Current
4
Ground Fault Trip
Fault SOS
Current
Fault SOS Current
5
Phase Loss Trip
Phase Loss
Accumulator
Phase Loss
Accumulator
6
Remote Trip
Bitmap 16-bit
7
Over-Temp Trip
Temperature
8
9
A
B
C
Aux Switch Opened
Bitmap
16-bit
D
E
Low Trip Voltage
Warning
Bitmap
16-bit
F Software
Fault
10
RAM Failure
Bitmap 16-bit
11
ROM Failure
Bitmap 16-bit
12
13
Rating Plug Missing
Bitmap 16-bit
14
Short Time Switch
Change
Bitmap
16-bit
15
Long Time Switch
Change
Bitmap
16-bit
16
Instant Switch change
Bitmap 16-bit
17 Module
Switch/Type
Change
Bitmap
16-bit
18
Short Time Delay
Switch Change
Bitmap
16-bit
19
Long Time Delay
Switch Change
Bitmap
16-bit
1A
Module Missing Trip