O-10 Control Word Profile

Select the interpretation of the control and status words

corresponding to the installed network. Only the selections valid

for the network installed in slot A will be visible in the keypad

display.

Option:

Function:

[0]

*

Drive Profile

[1]

PROFIdrive profile

[5]

ODVA

O-13 Configurable Status Word STW

Option:

Function:

This parameter enables configuration of bits

12 – 15 in the status word.

[0]

No function

[1]

*

Profile Default Function corresponds to the profile default

selected in O-10 Control Word Profile.

O-50 Coasting Select

Option:

Function:

Select control of the coasting function via the

terminals (digital input) and/or via the network.

[0]

Digit

Input

Activates Coast command via a digital input.

[1]

Bus

Activates Coast command via the serial

communication port or network option module.

[2]

Logic

AND

Activates Coast command via the network/serial

communication port, AND additionally via one

of the digital inputs.

[3]

*

Logic OR

Activates Coast command via the network/serial

communication port OR via one of the digital

inputs.

O-51 Quick Stop Select

Select control of the Quick Stop function via the terminals

(digital input) and/or via the network.

Option:

Function:

[0]

Digital Input

[1]

Bus

[2]

Logic AND

[3]

*

Logic OR

O-52 DC Brake Select

Option:

Function:

Select control of the DC brake via the terminals

(digital input) and/or via the network.

[0]

Digit

Input

ActivatesDC Brake command via a digital input.

[1]

Bus

ActivatesDC Brake command via the serial

communication port or network option module.

[2]

Logic

AND

ActivatesDC Brake command via the network/

serial communication port, AND additionally via

one of the digital inputs.

O-52 DC Brake Select

Option:

Function:

[3]

*

Logic OR

ActivatesDC Brake command via the network/

serial communication port OR via one of the

digital inputs.

O-53 Start Select

Option:

Function:

Select control of the drive start function via the

terminals (digital input) and/or via the network.

[0]

Digit

Input

Activates Start command via a digital input.

[1]

Bus

Activates Start command via the serial

communication port or network option module.

[2]

Logic

AND

Activates Start command via the network/serial

communication port, AND additionally via one

of the digital inputs.

[3]

*

Logic OR

Activates Start command via the network/serial

communication port OR via one of the digital

inputs.

O-54 Reversing Select

Option:

Function:

[0]

Digital

Input

Select control of the drive reverse function via

the terminals (digital input) and/or via the

network.

[1]

Bus

Activates the Reverse command via the serial

communication port or network option

module.

[2]

Logic AND

Activates the Reverse command via the

network/serial communication port, AND

additionally via one of the digital inputs.

[3]

*

Logic OR

Activates the Reverse command via the

network/serial communication port OR via one

of the digital inputs.

O-55 Set-up Select

Option:

Function:

Select control of the drive set-up selection via

the terminals (digital input) and/or via the

network.

[0]

Digit

Input

Activates the set-up selection via a digital input.

[1]

Bus

Activates the set-up selection via the serial

communication port or network option module.

[2]

Logic

AND

Activates the set-up selection via the network/

serial communication port, AND additionally via

one of the digital inputs.

[3]

*

Logic OR

Activate the set-up selection via the network/

serial communication port OR via one of the

digital inputs.