No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter
Reference
79
Illegal PS config
X
X
80
Drive Restored to Factory Settings
X
81
CSIV corrupt
82
CSIV parameter error
85
Profibus/Profisafe Error
90
Encoder Loss
(X)
(X)
EC-61 Feedback Signal Monitoring
91
Analog input 54 wrong settings
X
S202
243
Brake IGBT
X
X
244
Heatsink temp
X
X
X
245
Heatsink sensor
X
X
246
Pwr.card supply
X
X
247
Pwr.card temp
X
X
248
Illegal PS config
X
X
250
New spare part
X
251
New Model Number
X
X
Table 11.1 Alarm/Warning Code List
(X) Dependent on parameter
1) Can not be Auto reset via H-04 Auto-Reset (Times)
A trip is the action when an alarm has appeared. The trip will coast the motor and can be reset by pressing the reset
button or make a reset by a digital input (Parameter group E-1# [1]). The origin event that caused an alarm cannot damage
the frequency converter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause
damage to frequency converter or connected parts. A Trip Lock situation can only be reset by a power cycling.
LED indication
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Table 11.2
Warnings and Alarms
PROFINET Operating Instruction
66
11