GE Industrial Solutions AF-650 GP PROFINET User Manual

Page 67

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter

Reference

79

Illegal PS config

X

X

80

Drive Restored to Factory Settings

X

81

CSIV corrupt

82

CSIV parameter error

85

Profibus/Profisafe Error

90

Encoder Loss

(X)

(X)

EC-61 Feedback Signal Monitoring

91

Analog input 54 wrong settings

X

S202

243

Brake IGBT

X

X

244

Heatsink temp

X

X

X

245

Heatsink sensor

X

X

246

Pwr.card supply

X

X

247

Pwr.card temp

X

X

248

Illegal PS config

X

X

250

New spare part

X

251

New Model Number

X

X

Table 11.1 Alarm/Warning Code List

(X) Dependent on parameter

1) Can not be Auto reset via H-04 Auto-Reset (Times)

A trip is the action when an alarm has appeared. The trip will coast the motor and can be reset by pressing the reset
button or make a reset by a digital input (Parameter group E-1# [1]). The origin event that caused an alarm cannot damage
the frequency converter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause
damage to frequency converter or connected parts. A Trip Lock situation can only be reset by a power cycling.

LED indication

Warning

yellow

Alarm

flashing red

Trip locked

yellow and red

Table 11.2

Warnings and Alarms

PROFINET Operating Instruction

66

11

1

Advertising