Car2912te series front-end, Preliminary data sheet – GE Industrial Solutions CAR2912TE series User Manual

Page 17

Advertising
background image

GE

Preliminary Data Sheet

CAR2912TE series front-end

Input: 90Vac to 264Vac; Output: 12Vdc @ 2900W; 3.3 or 5Vdc @ 4A Standby

October 21, 2013

©2013 General Electric Company. All rights reserved.

Page 17

Read_Fan_speed (0 x D3) :

Returns the commanded speed in

percent and the measured speed in RPM. Up to 3 fans are
supported. If a fan does not exist, or if the command is not
supported the unit return 0x00.

1

8

1

8

1

S Slave address

Wr A Command 0xE1

A

1

8

1

8

1

Sr

Slave address

Rd

A

Byte count = 4

A

8

1

8

1

8

1

8

1

Adjustment % A Fan-1

A Fan-2

A Fan-3 A

8

1

1

PEC

NA

P


Read input string (0xD4):

Reads back the input voltage and

input power consumed by the power supply. In order to

improve the resolution of the input voltage reading the data is

shifted by 75V.

1

7

1

1

8

S

Slave address

Wr

A

Command Code 0xDC

1

1

7

1

1

A

Sr

Slave Address

Rd

A

8

1

8

1

8

1

Byte Count = 4 A Voltage - LSB A Voltage - MSB

A

8

1

8

1

8

1

1

Power - LSB

A Power - MSB A PEC No-ack P


Read_firmware_rev [0 x D5]:

Reads back the firmware

revision of the two µC in the power supply.

1

7

1

1

8

1

S

Slave address

Wr

A Command Code 0xDD A

1

1

7

1

1

8

1

A

Sr

Slave Address

Rd

A

Byte Count = 2

A

8

1

8

1

Primary micro revision

A

DSP revision

A

8

1

1

PEC

NA

P

For example; the read returns one byte for each device (i.e. 0

x 002114h ). The sequence is primary micro, DSP, and I

2

C

micro. 0x00 in the first byte indicates that revision information

for the primary micro is not supported. The number 21 for the

DSP indicates revision

2.1, and the number 14 for the i2c

micro indicates revision 1.4.

Read_run_timer [0 x D6]:

This command reads back the

recorded operational ON state of the power supply in hours.

The operational ON state is accumulated from the time the

power supply is initially programmed at the factory. The

power supply is in the operational ON state both when in

standby and when it delivers main output power. Recorded

capacity is approximately 10 years of operational state.

1

7

1

1

8

1

S Slave address

Wr

A Command Code 0xDE

A

1

7

1

1

8

1

Sr

Slave Address

Rd

A

Byte count = 3

A

8

1

8

1

8

1

Time - LSB

A

Time

A

Time - MSB

A

8

1

1

PEC

No-ack

P

EEPROM record (0xD9):

The µC contains 128 bytes of

reserved EEPROM space for customer use, such as a

customized set of FRU_ID parameters.
To write into the EEPROM section, after the command code,

the starting memory location must be entered followed by a

block write, and terminated by the PEC number;

1

8

1

8

1

S

Slave address

Wr A Command 0xD9

A

8

1

8

1

Memory location A

Byte count ≤ 32

A

8

1

8

1

8

1

1

Byte 1

A ………………….. Byte ≤ 32

A

PEC A

P

The highest memory location is address 128b.

To read contents from the EEPROM section

1

7

1

1

8

1

S Slave address

Wr

A Command 0xD9

A

8

1

8

1

Memory location A

Byte count ≤ 32

A

1

7

1

1

Sr

Slave address

Rd

A

8

1

8

1

Byte 1

A ………………………………………………….

Byte ≤ 32

A

8

1

1

PEC

No-ack P

Test Function (0xDF)

Bit

Function

State

0

LED test

1=ON, 0=OFF

1

reserved

2

reserved

3

reserved

4

Or’ing test

1=ON, 0=OFF

5

reserved

6

reserved

7

reserved

Advertising