*Install rivet in aligned holes with interlock roller, set at .670 and striker making contact with adjusted trip coil rod.
CAUTION: This is a safety feature not a routine maintenance item
Figure 22 Negative interlock
A change in the setting of the close latch stop bolt will
affect the adjustment of the spring discharge interlock
Figure 23 Spring wipe