I-t-e 1600 ampere black frame breakers only, Terminal, Assembly – GE Industrial Solutions ProTrip Conversion Kits K-225, K-600, K-800, K-1600 User Manual
Page 13: 1600 a black frame breakers, Ct assembly, 1600 a black frame breakers
I-T-E 1600 Ampere Black Frame Breakers Only
1. Attach the mounting brackets removed from the old
copper terminals in Section 3, step 6 of I-T-E 1600
Ampere Breakers, onto the insulated housings, using
the Philips-head screws removed in step 5, as shown
in Figure 20.
2. Attach a new copper load-terminal extension to each
insulated housing with the two
3
/
8
-16 x 1" bolts, lock
washers, and flat washers provided, as shown in
Figure 20.
3. Place a CT and insulating barrier over the copper
post on each housing. Secure the assembly with the
top copper bus and the
1
/
2
-13 x 1
1
/
2
" bolt, lock
washer, and flat washer provided, as shown in Figure
21. The bolt should be finger tight for now.
The remaining steps of this procedure are identical to
steps 5–9 for red frame breakers on the previous page.
Figure 20. Terminal assembly, 1600 A black frame
breakers.
Figure 21. CT assembly, 1600 A black frame breakers.
13