Connecting the Trip Unit Wiring Harness

1. Carefully rotate the breaker onto its back so that the

bottom of the breaker is accessible.

2. Run the wires comprising the trip unit wiring harness

along the front of the insulating barrier, then down to
the bottom of the breaker, as shown in Figure 33.

3. Join the four-pin connector on the trip unit harness to

the four-pin connector on the flux shifter, as shown in
Figure 33.

4. Connect the harness leads to the screw terminals on

each CT, as shown in Figure 33. The black wire (tap)
connects to the left terminal and the white wire
(common) to the right terminal.

5. Use the wire ties provided to tie the harness back

against the frame. The harness should be tied to the
holes in the fiber barriers at each CT. Ensure that the
wiring will not interfere with any moving parts.

Figure 33. Trip unit wiring harness installation.

Configuring the Trip Unit

See DEH-40034 for detailed instructions for setting up
ProTrip trip units.