GE Industrial Solutions Entellisys 4.0 System Test Kit User Manual User Manual
Page 42
![background image](/manuals/295498/42/background.png)
System Test Kit
42
* Entellisys Version 3.0 systems
** Entellisys Version 4.0 systems
Table 1-14 Default values for user-defined relay protection tests
User-Defined
Frequency / Multiplier / KW Range
Prefault
Fault
Post Fault
Over Frequency
50 Hz – 60 Hz
0.1 Hz increment
50 Hz – 70 Hz
0.1 Hz increment
50 Hz – 60 Hz
0.1 Hz increment
Under Frequency
50 Hz – 60 Hz
0.1 Hz increment
44 Hz – 60 Hz
0.1 Hz increment
50 Hz – 60 Hz
0.1 Hz increment
Overvoltage
96% to 104%
0.5% increment
104% to 132%
0.5% increment
96% to 104%
0.5% increment
Undervoltage
96% to 104%
0.5% increment
47.5% to 95%*
8.5% to 95%**
0.5% increment
96% to 104%
0.5% increment
Phase Loss
0% to 7%
1% increment
7% to 51%
1% increment
0% to 7%
1% increment
Power Reversal
0 to 100 KW
10 KW increment
0 to 1000 KW
10 KW increment
0 to 100 KW
10 KW increment
High Current
0% to 100%
5% increment
45% to 205%
5% increment
0% to 100%
5% increment